Air Circuit Breakers (ACB) – Technical Guide Based on IEC 60947-2

Standards:

  • IEC 60947-2
  • SBC 401 (Electrical Code – KSA)
  • IEEE 1015
  • NEC 240 (contextual comparison)

📘 1.0 What is an ACB?

Air Circuit Breakers (ACBs) are heavy-duty circuit protection devices used for main LV incomer, generator output, and bus-coupler protection in installations with current ratings from 800 A to 6300 A.

They interrupt fault current in air, using arc chutes and blowout devices. Modern ACBs feature electronic LSIG protection, remote control, communication, and zone-selective interlocking.


🧱 2.0 ACB Construction

Major Components:

  • Fixed & moving contacts
  • Arc chute with splitter plates
  • Blowout coil for arc displacement
  • Trip mechanism
  • Spring or motor charging system
  • Electronic trip unit (LSIG or LSIGM)
  • Plug-in/drawout chassis with mechanical interlock

📌 Construction resembles MCCBs but on a much larger scale with modular withdrawable design.


⚡ 3.0 Working Principle

OperationDescription
NormalCurrent flows through main contacts
FaultArc forms → arc chute splits & cools it → blowout coil deflects arc
TripElectronic unit sends signal → release mechanism opens contacts
ResetManual or motorized spring recharge resets breaker

Modern ACBs are remote-controlled, monitored, and fully programmable.


📚 4.0 IEC 60947-2 Clauses for ACBs

ClauseDescription
2.1.3Icu (Ultimate breaking capacity)
2.1.4Ics (Service breaking capacity)
4.3Dielectric strength
4.4.1Time-current coordination (LSIG trip unit)
4.5.2Selectivity and backup protection

ACBs must meet Type B or Type A coordination depending on backup breaker.


🔌 5.0 Ratings & Settings

TermDescription
InmFrame rating (e.g., 1600A, 3200A, 6300A)
IrLong-time adjustable protection (40–100% of Inm)
IsdShort-time delay protection (2–10× Ir)
IiInstantaneous trip (5–20× Ir or disabled)
IgGround fault trip (20–100% of Ir)
IcwWithstand current for 1s or 3s

📌 Example:
A 3200A ACB may be set at Ir = 2800A, Ii = 14,000A, Ig = 640A


🔧 6.0 LSIG Trip Functions

Trip Unit: L = Long | S = Short | I = Instant | G = Ground

ProtectionAdjustableRange
Long-time0.4–1 × Inm
Short-time2–10 × Ir
Instantaneous✅ or Disabled5–20 × Ir
Ground Fault20–100% Ir
Delay (sec)0.05 – 1.0 s

Most ACBs include Zone-Selective Interlocking (ZSI) to improve selectivity.


🧠 7.0 Application Chart

ApplicationACB SizeNotes
LV Main Incomer2500–6300 AFeeds MSB
Generator Output1600–3200 ASync-enabled
Transformer Secondary800–2500 AWith ZSI
Tie Breaker1600–3200 AWith interlocking
Bus-Coupler2500–4000 AAuto transfer logic

✅ ACBs are preferred at critical points, with high fault levels (>50kA) and advanced control needs.


🏆 8.0 Top ACB Brands & Models

BrandACB ModelRange
Schneider ElectricMasterPact MTZUp to 6300 A
ABBEmax 2Up to 6300 A
Siemens3WLUp to 6300 A
TerasakiTemPower 2800–6300 A
EatonNRX SeriesUp to 4000 A

All are IEC 60947-2 compliant and available with advanced trip units (Micrologic, PR123, ETU800, etc.)


📊 9.0 ACB vs MCCB

FeatureACBMCCB
Max CurrentUp to 6300 AUp to 2500 A
Trip UnitElectronic (LSIG)Thermal-Mag or Electronic
InstallWithdrawableFixed/Mounted
Arc QuenchingAirMagnetic blow-out
MonitoringFully programmableLimited (in thermal-magnetic)
CoordinationZSI, GFLBasic selectivity

📎 10.0 Final Notes

✅ Always ensure:

  • ACB matches the short-circuit level at its location (Icu ≥ fault level)
  • Set LSIG based on coordination study
  • ZSI enabled for backup protection
  • Breakers are tested under IEC 60947-2 and SBC 401-compliant

📚 References

  • IEC 60947-2: Low-voltage switchgear – Circuit Breakers
  • SBC 401 – Saudi Building Code (Electrical)
  • ABB Emax E2/E4/E6 catalogs
  • Schneider Electric MasterPact MTZ handbook
  • Siemens 3WL selection guide
  • IEEE 1015 – Application of Low-Voltage CBs

Leave a Comment